Skip to content
Maintenance and reliability

Epoxy flooring cost for factories and food plants: what sets the price per m², and what the quote must specify

In short

Epoxy flooring cost in South Africa is driven by thickness and surface preparation. A public research body awarded R754,193 on a request that closed in September 2024 to replace a cracked 745 m² epoxy floor with self-levelling epoxy of at least 2 mm: about R1,012 per m² by division. Concrete moisture, grinding and joints decide whether the floor lasts.

What work do you need done?

Headcore7 min read7 sources

How much does epoxy flooring cost per m² in South Africa?

In practice, a public buyer's award gives the clearest dated figure. The CSIR awarded RFQ 6366, which closed on 20 September 2024, at R754,193.00 for 745 m² at the Cofimvaba Science Centre in the Eastern Cape. Dividing the award by the area gives about R1,012 per m², a calculation the CSIR does not publish. The award page does not state whether VAT is included.[3][4]

The CSIR price covered removing an epoxy floor that was cracked and lifting, preparing the substrate, an epoxy primer and a self-levelling epoxy coat of at least 2 mm. It also covered cleaning, removal of construction waste and travel, with the work to be finished within two weeks.[4]

The CSIR's requests price the floor in two lines per square metre, quoted excluding VAT: in 2026, floor preparation, and supplying and installing the flooring with labour. The CSIR's 2026 request for 392 m² of 1 mm self-levelling epoxy at a hemp processing facility in Bergville, KwaZulu-Natal, is laid out that way.[5]

Which industrial floor coating systems do public buyers specify?

Three CSIR requests between 2022 and 2026 specified self-levelling resin floors from 4 mm of polyurethane, the thickest, to 1 mm of epoxy, the thinnest. The thickness is the first thing to fix in a request, because it sets the material per square metre.[6][4][5]

Which industrial floor coating systems do public buyers specify?
System and thicknessWhere it was specifiedAreaRequest and year
Self-levelling polyurethane, 4 mm, on a primerWorkshop floors, all in polyurethane (option 1) or part of a split with epoxy (option 2)400 m² (option 1) or 185 m² (option 2)CSIR RFQ 5797, 2022 (later withdrawn and reissued)
Self-levelling epoxy, at least 2 mm, on a solvent-free epoxy primerScience centre exhibition hall, replacing a cracked floor745 m²CSIR RFQ 6366, 2024 (awarded)
Self-levelling epoxy, 2 mm, on an epoxy primerWorkshop floors, the epoxy part of option 2215 m²CSIR RFQ 5797, 2022 (later withdrawn and reissued)
Self-levelling epoxy, 1 mm dry film, on a 0.25 mm epoxy primer, with epoxy covingHemp processing facility, with joints sealed for good manufacturing practice392 m²CSIR RFQ 6644.1, 2026

Sources:[6][4][5]

What does the law require of a food plant floor?

In South Africa, the floor of a food-handling area must "not have open joints or open seams and must be made of smooth, rust-free, non-toxic, cleanable and non-absorbent material that is dust-proof and water-resistant" (R638 of 2018, regulation 5(3)(a)(i)).[1]

The same regulation requires the floor to be of such a nature that it cannot contaminate food (regulation 5(3)(a)(ii)). A food premises must be built, finished and maintained so that it can be used without creating a health hazard (regulation 5(2)).[1]

Epoxy or polyurethane: which floor for a food plant?

In South Africa, public buyers have specified both resins, and R638 of 2018 names neither. The CSIR's 2022 workshop request specified 4 mm of self-levelling polyurethane, and its 2026 request for a processing facility 1 mm of self-levelling epoxy. Where floors take hot water or steam, put the cleaning temperature in the request and ask each quote to state the coating's temperature limit.[1][6][5]

The details at the edges count as much as the coating. The CSIR's 2026 Bergville request asked for 75 mm by 75 mm radius coving in epoxy mortar to run the floor into the wall without a joint. It also asked for about 142 m of existing joints to be re-cut and sealed with a hybrid polyurethane sealant.[5]

What surface preparation does an epoxy floor need?

In practice, the concrete must be sound, dry and ground back to clean material before any resin goes down. The CSIR's 2024 specification required surfaces that are clean, sound, free of laitance and dust, with a moisture content of no more than 4%. Its 2026 specification allowed less than 6%, measured before application, on concrete of at least 25 N/mm² compressive strength.[4][5]

The 2026 request specified diamond grinding for a mechanical key and an industrial vacuum during grinding to keep the area dust-free. It also called for cracks and cavities to be filled with an epoxy-based filler, and for the existing 1 mm of epoxy and 1 mm of the concrete to be ground off.[5]

The same request asked for thickness as dry film thickness rather than a nominal figure, so the finished floor can be measured against the order.[5]

How long is the floor out of use?

Plan for the area to be closed for the whole job: both CSIR epoxy floors, 745 m² in 2024 and 392 m² in 2026, were to be completed within two weeks of starting on site.[4][5]

Each coat needs its own curing time before the next: the 2026 specification set a minimum of eight hours for the primer before the self-levelling coat. Ask each quote for the cure time to foot traffic, to vehicles and to cleaning chemicals.[5]

Once in use, a smooth sealed floor suits a floor washer scrubber: one maker's scrubber range guide says disc brushes are ideal for smooth, even floors.[7]

Which safety rules apply while the coating is applied?

Resin coatings and grinding dust fall under the Regulations for Hazardous Chemical Agents (GN R. 280 of 2021). The employer must assess whether employees may be exposed, by any route of intake, and repeat the assessment at intervals not exceeding two years (regulation 5(1)).[2]

Exposure must be prevented or, where that is not reasonably practicable, adequately controlled, including by using a substitute, limiting who is exposed and for how long, and installing local extraction ventilation (regulation 10(1) and (2)).[2]

The employer must obtain the safety data sheet for each product from its supplier and give it to everyone who uses it or may be exposed to it (regulation 14A(1)(d)). The employer must also train exposed employees before work starts (regulation 3(1)).[2]

Where grinding dust contains crystalline silica, quartz carries a maximum occupational exposure limit of 0.1 mg/m³ in the respirable fraction, as an eight-hour time-weighted average (Annexure 2, Table 2).[2]

What to put in your request

  • The area in m², the room's use (dry production, washdown, cold store, warehouse) and the cleaning water temperature.[5]
  • The system and thickness: epoxy or polyurethane, self-levelling or coating, in mm of dry film thickness.[6][5]
  • The existing floor: an old coating to remove, cracks, and the concrete's strength and moisture reading.[4][5]
  • Preparation: grinding method, dust extraction, crack filling and the maximum moisture content before priming.[4][5]
  • Joints, coving, skirting and markings: metres of joints to re-cut and seal, coving size, skirting height, and demarcation lines.[6][5]
  • For food areas: a jointless, smooth, non-absorbent, water-resistant finish as R638 requires.[1]
  • Two price lines per m², preparation and supply-and-install, each excluding VAT, plus waste removal and travel.[5][4]
  • The dates the area is free, the time each coat needs to cure, and when it can take traffic and cleaning.[5]
  • Safety: the risk assessment, safety data sheets, dust extraction and ventilation, and operator training.[2]

Questions buyers ask

How much does an epoxy floor cost per square metre?

Dated public figures are scarce. The CSIR awarded R754,193.00 on a request that closed in September 2024 to remove a cracked 745 m² floor and lay at least 2 mm of self-levelling epoxy. Divided by the area, that is about R1,012 per m²; the award page does not state the VAT basis. A thinner coat on a sound slab costs less, extra preparation more.[3][4]

How dry must concrete be before an epoxy floor?

Public specifications set a limit and require it to be checked. The CSIR's 2024 specification allowed a maximum moisture content of 4%, and its 2026 specification less than 6%, measured before application, on concrete of at least 25 N/mm².[4][5]

Is epoxy allowed on a food factory floor?

R638 of 2018 does not name materials. It requires food-handling floors without open joints or seams, smooth, non-toxic, cleanable, non-absorbent, dust-proof and water-resistant, and unable to contaminate food (regulation 5(3)(a)). The CSIR's 2026 request for a processing facility specified self-levelling epoxy with coving and re-cut, sealed joints to meet good manufacturing practice.[1][5]

What work do you need done?

Sources

  1. Department of Health (Government Gazette 41730), Regulations governing general hygiene requirements for food premises, the transport of food and related matters (R. 638), 22 June 2018.
  2. Department of Employment and Labour (Government Gazette 44348), Regulations for Hazardous Chemical Agents (GN R. 280), 29 March 2021.
  3. CSIR, RFQ 6366: construction of minor works for the repair (removal and installation) of the epoxy floor in the Cofimvaba Science Centre (tender page, awarded), Closing date 20 September 2024.
  4. CSIR, Request for quotation (minor works) RFQ 6366: repair of the epoxy floor in the Cofimvaba Science Centre, Eastern Cape (scope, specification and pricing schedule), 28 August 2024.
  5. CSIR, RFQ 6644.1-09-03-2026: supply and installation of a specialised 1 mm self-levelling epoxy flooring system at the hemp processing centre, Bergville, 20 February 2026.
  6. CSIR, RFQ 5797: coating of workshop and laboratory floors using polyurethane and/or epoxy at building 12C (later withdrawn), Closing date 10 February 2022.
  7. Alfred Kärcher SE & Co. KG, Scrubber driers: category brochure (professional range), November 2019.