Gas fire suppression system for a server or plant room: agents, safety, the HFC phase-down and servicing

In short

A gas fire suppression system floods a closed room with an extinguishing agent when a fire is detected. In South Africa, the clean agents follow the SANS 14520 series; carbon dioxide is lethal at its design concentration. HFC-227ea falls under the Kigali phase-down South Africa ratified in 2019, so ask about refill supply before you choose.

Headcore6 min read17 sources

Which gas suppression system suits a server or plant room?

The one whose agent suits the room's people, leaks and future refills. A gas fire suppression system is a fixed installation that discharges an extinguishing gas into a closed room when it detects a fire.[15][14]

In South Africa, the SANS 14520 series covers gaseous fire-extinguishing systems, one part per agent. Part 1, the general requirements, is SANS 14520-1:2026, edition 4, approved by the SABS on 30 March 2026.[1]

The agents fall into three groups: halocarbons such as HFC-227ea and FK-5-1-12, inert gases such as IG-541, IG-55 and IG-100, and carbon dioxide. Each later part of SANS 14520 covers the physical properties and system design for its agent.[1][2][3][4]

Portable equipment in the same room is a separate duty, covered by the fire extinguisher service page.[14]

How do the common suppression agents compare on global warming potential?

HFC-23 has the highest 100-year global warming potential below, at 14,800; the inert gases have the lowest, at zero. The Kigali Amendment gives the HFC figures, and the US EPA's SNAP list the others.[5][12]

How do the common suppression agents compare on global warming potential?
AgentType100-year GWPSouth African standard (edition, approved)
HFC-23Halocarbon (HFC)14,800SANS 14520-10:2026 (ed. 4, 29 May 2026)
HFC-227eaHalocarbon (HFC)3,220SANS 14520-9:2019 (ed. 3, 17 December 2019)
Carbon dioxideCarbon dioxide (lethal at design concentration)1Not part of SANS 14520
FK-5-1-12Halocarbon (fluoroketone)Under 1SANS 14520-5:2026 (ed. 3, 29 May 2026)
IG-541Inert gas blend0SANS 14520-15:2019 (ed. 3, 17 December 2019)
IG-55Inert gas blend0SANS 14520-14:2019 (ed. 3, 17 December 2019)
IG-100Inert gas0SANS 14520-13:2019 (ed. 3, 17 December 2019)

Sources:[5][12][1][2][3][4]

Is a gas suppression system safe for people in the room?

It depends on the agent, and carbon dioxide is the dangerous one. The US Environmental Protection Agency reported in February 2000 that carbon dioxide is lethal at its minimum total-flooding design concentration of 34%.[11]

The same EPA report states that above 17% carbon dioxide, unconsciousness, convulsions and death occur within one minute of breathing it. It found 51 incident records from 1975 to 2000, with 72 deaths and 145 injuries from carbon dioxide system discharges.[11]

For the other agents, the EPA's SNAP list points to the NFPA 2001 safety guidelines. It also limits an IG-541 design concentration to no more than 5% carbon dioxide.[12][1]

In South Africa, section 8 of the Occupational Health and Safety Act requires a workplace safe and without risk, as far as reasonably practicable. Section 8(2)(b) asks the employer to eliminate or mitigate a hazard before resorting to protective equipment. The same OHS Act sets duties towards the contractors who service the system.[10]

Are HFC suppression gases being phased out in South Africa?

Yes, gradually, under the Kigali Amendment, which South Africa ratified on 1 August 2019. The UN Ozone Secretariat records that South Africa reported its HFC licensing system on 19 April 2022.[7]

Kigali lists HFC-227ea and HFC-23 among the controlled HFCs. South Africa is not one of the ten developing countries given the later schedule in decision XXVIII/2, so the earlier one applies.[5][6]

That schedule caps HFC consumption from 2024 at a baseline built from the average 2020 to 2022 HFC consumption, plus 65% of the HCFC baseline. The cap falls to 90% in 2029, 70% in 2035, 50% in 2040 and 20% from 2045.[5]

Halons are treated more strictly, as ozone-depleting substances. Regulation 3(1)(c) of South Africa's 2014 ozone regulations prohibits producing, importing, using or selling halons unless for a critical use.[8]

Halons reclaimed from existing fire protection systems before the 2014 regulations took effect are exempt (regulation 3(2)). Using recovered halons in an existing system needs the Director-General's approval (regulation 3(3)). The 2021 amendment's list names Halon 1211, 1301 and 2402.[8][9]

What is a room integrity test?

A room integrity test is a door fan test that predicts how long the agent will stay in the room after a discharge. In practice, ISO 14520 and other clean-agent standards recognise it as part of system acceptance.[13]

A fan in a doorway blows air out of the room, then in, at a small test pressure. Software turns the flow and pressure readings into an equivalent leakage area and a predicted retention time.[13]

The test maker's guidance is to repeat the test every year, and whenever new holes are made in the room's walls, floor or ceiling.[13]

How is a gas suppression system serviced, and by whom?

At least yearly, by a competent person. Johannesburg requires every service installation, including an automatic fire-extinguishing installation, to be inspected at least every 12 months by a registered, competent person (section 16(1)(c)(iii)).[14]

Johannesburg also requires servicing to the manufacturer's specifications. After each service, the technician must certify in writing that the installation is fully functional (section 16(2)).[14]

eThekwini's Fire By-law, 2022 lists gaseous, powder and foam systems at a 12-monthly interval, to SANS 14520 and the manufacturer's specifications. The technician must be registered with a body the Municipality recognises (section 31(1)).[16][14]

Occupants must be told before a test of any alarm part of the system. Cape Town also requires notice to the parties who monitor the system (section 18(2)).[15][16][14]

What to put in your request

  • The room's use (server, control, plant or archive room), its size, and whether people work in it.[11][10]
  • The agent installed now, the number and size of cylinders, and the last refill date.[1]
  • The date and result of the last room integrity test, and any new cable or duct openings since then.[13]
  • For HFC-227ea systems: the supplier's refill source, given the HFC phase-down.[5][7]
  • For any halon still in place: proof of the Director-General's approval, or a plan to replace it.[8]
  • The technician's registration with a body your metro recognises, and the company's.[16][17]
  • A written certificate that the installation is fully functional after the service.[14][16]
  • Who isolates the discharge during the visit, and who tells occupants and the monitoring party.[15][16]

Questions buyers ask

What is the best fire suppression system for a server room?

No single agent is best for every room. Inert gases have zero global warming potential; HFC-227ea falls under the Kigali phase-down; FK-5-1-12 has a GWP under 1. Carbon dioxide is lethal at its design concentration. Match the agent to the room's tightness, occupancy and refill supply.[12][5][11]

How often must a gas suppression system be serviced?

Johannesburg and eThekwini both require at least a yearly inspection or service. In practice, the room integrity test is repeated yearly too, and whenever new openings are made.[14][16][13]

Do gas suppression technicians need SAQCC Fire registration?

eThekwini requires registration with a body the Municipality recognises. In practice, public tenders ask for it by name. A research council's tender of November 2022 required SAQCC Fire and Gas certificates for company and technician.[16][17]

Can I keep an old halon system?

Only within the 2014 ozone regulations. Halon reclaimed from existing fire protection systems before the regulations took effect is exempt. Using recovered halon in an existing system needs the Director-General's approval.[8]

Sources

  1. South African Bureau of Standards (SABS webstore), SANS 14520-1:2026 (Ed. 4.00), Gaseous fire-extinguishing systems: Physical properties and system design, Part 1: General requirements, 30 March 2026.
  2. South African Bureau of Standards (SABS webstore), SANS 14520-9:2019 (Ed. 3.00), Part 9: HFC 227ea extinguishant, 17 December 2019.
  3. South African Bureau of Standards (SABS webstore), SANS 14520-5:2026 (Ed. 3.00), Part 5: FK-5-1-12 extinguishant, 29 May 2026.
  4. South African Bureau of Standards (SABS webstore), SANS 14520 parts 10 (HFC 23, 2026), 13 (IG-100, 2019), 14 (IG-55, 2019) and 15 (IG-541, 2019): webstore listings, 17 December 2019 to 29 May 2026.
  5. UNEP Ozone Secretariat, The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties, 15 October 2016.
  6. UNEP Ozone Secretariat, Decision XXVIII/2: Decision related to the amendment phasing down hydrofluorocarbons, 15 October 2016.
  7. UNEP Ozone Secretariat, Country profile: South Africa (ratifications and licensing system), accessed November 2026.
  8. Department of Environmental Affairs (Government Gazette 37621), Regulations regarding the Phasing-Out and Management of Ozone Depleting Substances (GN 351), under the National Environmental Management: Air Quality Act, 8 May 2014.
  9. Department of Environment, Forestry and Fisheries (Government Gazette 44065), Amendments to the Regulations regarding the Phasing-Out and Management of Ozone Depleting Substances (GN 10), 11 January 2021.
  10. Government Gazette 14918, Occupational Health and Safety Act 85 of 1993, 2 July 1993.
  11. US Environmental Protection Agency, Carbon Dioxide as a Fire Suppressant: Examining the Risks (EPA430-R-00-002), February 2000.
  12. US Environmental Protection Agency, SNAP: substitutes in total flooding agents, 18 March 2026.
  13. Retrotec, Testing enclosures: overview of a door fan test, 12 July 2010.
  14. City of Johannesburg Metropolitan Municipality, Emergency Services By-laws (Notice 826, Gauteng Provincial Gazette Extraordinary 179, as amended by Notice 1118 of 31 August 2011), 21 May 2004, as amended 31 August 2011.
  15. Open By-laws (Laws.Africa), City of Cape Town, Community Fire Safety By-law, 2002 (version as at 21 August 2015), 21 August 2015.
  16. Open By-laws (Laws.Africa), eThekwini Municipality, Fire By-law, 2022 (version as at 27 October 2022), 27 October 2022.
  17. CSIR, RFP No. 3547/02/12/2022: servicing and maintenance of fire detection, gas fire suppression systems and sprinkler systems, CSIR Gauteng sites, 11 November 2022.