Lightning conductor: what it is, the parts of a lightning protection system and what to ask before work starts
In short
A lightning conductor is the metal rod or conductor on a structure that is meant to take a lightning strike. It is only the first part of a lightning protection system: air termination, down conductors and earth termination. Surge protection inside may be needed as well. In South Africa the standards are SANS 10313 and the SANS 62305 series.
Tell us about the electrical work
Headcore5 min read11 sources
What is a lightning conductor?
A lightning conductor is, in British English, the same thing as a lightning rod: "a metal rod mounted on a structure and intended to protect it from a lightning strike". The rod works only when it is connected to earth.[11]
South African standards and trade writing use a wider term, the lightning protection system (LPS). A South African trade article describes its external part as an air termination system to intercept the strike, a down conductor system to carry the charge to ground and an earth termination system to improve the path of the charge into the ground.[1][9]
What are the parts of a lightning protection system?
The external system has three parts, and the structure may need protection measures inside as well.[9]
| Part | What it does |
|---|---|
| Air termination | Intercepts the lightning strike; the air terminals are usually placed at or along the upper points of a roof structure |
| Down conductors | Carry the charge to ground, connected by the most direct route to one or more earthing terminals |
| Earth termination | Improves the path of the charge into the ground; earthing rods, plates or mesh |
| Surge protection measures | Protect electrical and electronic systems inside the structure; surge protection means more than lightning surge protection |
Which standards cover lightning protection in South Africa?
Two South African standards cover the physical protection of a structure. SANS 10313:2018 (Ed. 3.03, reaffirmed in November 2023) provides requirements for protection against physical damage by a lightning protection system and against injury to living beings from touch and step voltages near it, and its scope includes thatched roof structures and buildings with explosive or flammable substances.[1]
SANS 62305-3:2025 (Ed. 3.00) covers physical damage to structures and life hazard in the same way. The SANS 62305 series has four parts: general principles, risk management, physical damage to structures and life hazard, and electrical and electronic systems within structures. Each part is a 2025 edition approved on 2 September 2025.[4][2][3][5]
Earth electrodes have their own standard, SANS 10199:2016, and SANS 10142-1 is the wiring code for the installation inside. How earth resistance and earth tests are done is a separate job from the lightning protection system itself.[6][7]
Does a building or plant need a lightning conductor?
In practice, the answer comes from a risk assessment. A South African trade article puts it as "lightning protection is an active exercise in risk management", and says the designer will propose a lightning protection system, surge protection measures or both together, where the risk treatment is deemed necessary.[9]
Part 2 of SANS 62305 is the risk part: it provides a procedure to evaluate the risk to a structure from lightning flashes to earth and to select protection measures that reduce it to or below the tolerable limit. To ask companies for the design or installation, post a request for lightning protection.[3]
What about plant and equipment on the roof?
Roof-mounted plant such as ventilation and air conditioning equipment is a known trouble spot. A South African trade paper explains that if roof equipment is connected directly to the external system, a direct strike sends partial lightning currents into the structure, which can destroy surge-sensitive equipment, raise step and touch hazards and raise the risk of fire.[10]
The same paper describes the alternative, an isolated air termination system: a separation distance is calculated and kept between the equipment and the air terminal. The separation distance has to be taken into account when the air termination is dimensioned, so say on a request that there is plant on the roof.[10]
How does lightning protection show on an electrical CoC?
The Electrical Conformance Board's test report template for SANS 10142-1 installations asks whether surge protection is installed and whether lightning protection is installed. If applicable, the form says to complete Table I.10, the lightning protection system installation safety report.[8]
So where lightning protection is installed, the test report that goes with the electrical certificate of compliance points to a further report for it, Table I.10. The CoC article explains who may sign the certificate.[8]
What to ask a lightning protection supplier
- Whether you want a risk assessment and a design, or an existing design installed, and the standard and edition each will follow (SANS 10313 or SANS 62305).[1][3][4]
- What the structure is for, its size and height, its roof and cladding, and what or who is inside, including thatch or flammable or explosive material.[1]
- Whether the job includes protection of the electrical and electronic systems inside the structure, as well as the external system.[5][9]
- Plant or equipment on the roof, and how the design keeps lightning current out of it, for example by a separation distance.[10]
- Any existing system: drawings, the date and result of the last inspection, and the earth test results (SANS 10199 covers the earth electrodes).[6]
- The report you need at handover, and whether the electrical installation's test report must show Table I.10.[8]
Questions buyers ask
Is a lightning conductor the same as a lightning protection system?
No. The conductor or rod is the air termination, the part that intercepts the strike. The system adds down conductors and an earth termination, and the structure may need surge protection measures inside as well.[9][11]
Does a lightning conductor protect the equipment inside?
Not by itself. SANS 62305-4 deals with the protection of electrical and electronic systems within structures from lightning electromagnetic impulse, and a South African trade article stresses that surge protection means more than lightning surge protection. Surge protection devices are one such measure.[5][9]
Tell us about the electrical work
Sources
- SABS, SANS 10313:2018 (Ed. 3.03), Protection against lightning: physical damage to structures and life hazard (catalogue entry with scope; reaffirmed 24 November 2023), 18 July 2018.
- SABS, SANS 62305-1:2025 (Ed. 3.00), Protection against lightning Part 1: General principles, 2 September 2025.
- SABS, SANS 62305-2:2025 (Ed. 3.00), Protection against lightning Part 2: Risk management, 2 September 2025.
- SABS, SANS 62305-3:2025 (Ed. 3.00), Protection against lightning Part 3: Physical damage to structures and life hazard, 2 September 2025.
- SABS, SANS 62305-4:2025 (Ed. 3.00), Protection against lightning Part 4: Electrical and electronic systems within structures, 2 September 2025.
- SABS, SANS 10199:2016 (Ed. 2.02), The design and installation of earth electrodes, 14 March 2016.
- SABS, SANS 10142-1:2026 (Ed. 3.03), The wiring of premises Part 1: Low-voltage installations, 24 June 2026.
- Electrical Conformance Board of South Africa, Test report for all general electrical installations to SANS 10142-1 (template), undated, read November 2026.
- Crown Publications, Sparks Electrical News (article by the National Director of the Earthing and Lightning Protection Association), Lightning protection: understanding the risk, applying the correct solution, 5 April 2022.
- Crown Publications, Electricity+Control, Lightning protection: the 'Separation Distance' concept, January 2016.
- Wikipedia, Lightning rod, undated, read November 2026.