In short

A surge protection device (SPD) limits a voltage spike on a power circuit by diverting the surge current to earth or absorbing it. Devices are tested in classes I, II and III. They are fitted at the supply entrance, at distribution boards and at the equipment, and they do not replace a lightning protection system.

Tell us about the electrical work

Headcore5 min read8 sources

What does a surge protection device do?

A surge protector protects electrical devices in alternating current circuits "from voltage spikes", lasting microseconds. For industrial and utility equipment the terms in use are surge protection device (SPD) and transient voltage surge suppressor.[8]

It limits the voltage by short-circuiting the current to ground or absorbing the spike. A metal-oxide varistor conducts large currents when the voltage across it rises above its rating, and the energy of the spike ends up in the power lines, the ground or the protector, as heat.[8]

A surge arrester is itself connected to ground and works by routing the energy of an overvoltage transient to ground. How earth tests are done and recorded is covered separately.[8]

What do SPD types and classes mean?

The type of a device relates to the tests it must be able to meet: a UK certification body's guide calls a device that meets test Class I a Type 1 SPD, and so on. The test waveforms are those of IEC 61643-11, which SANS 61643-11 is related to.[7][1]

What do SPD types and classes mean?
Class (type)Test it is built to meetWhat the test stands for
Class I (Type 1)10/350 microsecond current impulseA standard lightning impulse; a lightning fault current has this waveform
Class II (Type 2)Discharge current In with an 8/20 microsecond impulseAn induced surge current has this waveform
Class III (Type 3)1.2/50 microsecond voltage with an 8/20 microsecond current, as a combination waveA combined voltage and current test

Sources:[7][6]

Where does a surge protection device go in a plant?

In practice, devices sit at more than one point. A UK certification body's guide to the UK wiring rules puts Type 1 devices as close as possible to the origin of the installation where protection against direct lightning currents is needed, for example in a building with a lightning protection system. In industrial installations Type 2 devices may also go on sub-distribution boards or closer to the equipment, and Type 3 devices near or within sensitive equipment, only where Type 1 or 2 devices sit upstream.[7]

A South African trade article makes a related point: a surge protective device in a distribution board that is used for equipotential bonding does not constitute a surge protection measure (SPM). It also says surge protection means considerably more than lightning surge protection.[5]

SANS 61643-12:2021 (Ed. 3.00) is the standard on the selection, operation, location and coordination of SPDs on 50/60 Hz AC power circuits and equipment rated up to 1 000 V RMS.[2]

Is a surge protection device the same as lightning protection?

No. One general source says surge arresters are "not generally designed to protect against a direct lightning strike to a conductor": they protect against transients from strikes in the vicinity, which lightning can induce in buried and in overhead conductors. The exception is a device that meets test Class I: the UK guide says Type 1 devices are designed to divert the high surge currents associated with direct lightning strikes to earth safely.[8][7]

The external parts of a lightning protection system, the air termination, down conductors and earth termination, are a separate set of measures. The lightning conductor article describes them. A structure that needs the external system as well can ask for lightning protection.[5]

SANS 62305-4:2025 (Ed. 3.00) provides information for the design, installation, inspection, maintenance and testing of the protection of electrical and electronic systems within structures, to reduce the risk of permanent failures caused by lightning electromagnetic impulse. SANS 61643-11:2026 (Ed. 2.00, approved 2 March 2026) applies to devices for surge protection against indirect and direct effects of lightning or other transient overvoltages.[3][1]

How does a surge protection device show on the electrical paperwork?

The Electrical Conformance Board's test report template for SANS 10142-1 installations asks whether surge protection is installed, with a reference to clause 6.7.6 and annex I of the standard. It asks the same of lightning protection and, if applicable, for Table I.10, the lightning protection system installation safety report.[4]

Ask the supplier what record of the devices, their positions and their classes you will receive: the template itself asks only whether surge protection is installed.[4]

What to put in a request for surge protection

  • The supply: the voltage and the earthing system of the installation, the main board and the sub-boards that feed the equipment to be protected.[2][7]
  • Whether the structure has a lightning protection system, with its drawings and last inspection record, since a device is not a substitute for one.[8][5]
  • Whether devices are wanted at the supply entrance, at the distribution boards, at the equipment or in stages, and the standard and edition they must meet (SANS 61643-11).[7][1]
  • Earthing: the state of the earth electrode and the date and result of the last earth test.[8]
  • The record you need at handover and who will ask for it, including what the electrical installation's test report records about surge protection.[4]

Questions buyers ask

Is a surge protection device the same as a surge arrester?

In industrial and utility use the terms are used for the same kind of device. The general description of a surge protector names both the surge protection device and the surge arrester.[8]

Does a surge protection device stop a direct lightning strike?

No. A direct strike to a structure is the job of its lightning protection system. Surge arresters are not generally designed to protect against a direct strike to a conductor; a Type 1 device is built to divert the high surge currents that a direct strike sends into the installation, as one of the surge protection measures for the equipment inside.[8][7][5]

Which South African standards apply to surge protection devices?

SANS 61643-11:2026 (Ed. 2.00) for the devices, SANS 61643-12:2021 (Ed. 3.00) for their selection and application, and SANS 62305-4:2025 (Ed. 3.00) for the protection of systems inside a structure from lightning impulses.[1][2][3]

Tell us about the electrical work

Sources

  1. SABS, SANS 61643-11:2026 (Ed. 2.00), Low-voltage surge protective devices Part 11: Surge protective devices connected to low-voltage power systems, requirements and test methods (catalogue entry with scope), 2 March 2026.
  2. SABS, SANS 61643-12:2021 (Ed. 3.00), Low-voltage surge protective devices Part 12: Surge protective devices connected to low-voltage power systems, selection and application principles (catalogue entry with scope), 13 April 2021.
  3. SABS, SANS 62305-4:2025 (Ed. 3.00), Protection against lightning Part 4: Electrical and electronic systems within structures (catalogue entry with scope), 2 September 2025.
  4. Electrical Conformance Board of South Africa, Test report for all general electrical installations to SANS 10142-1 (template), undated, read November 2026.
  5. Crown Publications, Sparks Electrical News (article by the National Director of the Earthing and Lightning Protection Association), Lightning protection: understanding the risk, applying the correct solution, 5 April 2022.
  6. Crown Publications, Electricity+Control, Lightning protection: the 'Separation Distance' concept, January 2016.
  7. NICEIC (UK electrical contracting certification body), Types of SPD and their use in electrical installations, 16 July 2024.
  8. Wikipedia, Surge protector, undated, read November 2026.