What does kVA mean, and how does it differ from kW?

kVA: the unit of apparent power, the product of voltage and current, in which generators and electricity supplies are rated; kW is kVA times the power factor, 0.8 on the three-phase sets read here.[1][2][3][5]

Also called Kilovolt-ampere, Apparent power, Generator rating

  • kVA is apparent power and kW is real power. The sheet and papers read here rate three-phase generator sets at 0.8 power factor, so one maker's 80 kVA set is rated 82.5 kVA and 66 kW for prime power at 400 V.
  • Three-phase current is kVA times 1000, divided by 1.732 times the volts: 82.5 kVA at 400 V is 119.1 A, the figure on the maker's sheet. Single-phase supplies skip the 1.732.
  • The national utility sizes its smaller business supplies in kVA and bills several charges per kVA on its large time-of-use tariff. A hired set needs its kW load, its biggest motor start, single or three phase, and prime or standby rating stated in the request.

Need one?Generator hire: sizes and rulesPlant hire

Headcore8 sources

Tell us about the power you need

What does kVA mean, and why is it not the same as kW?

kVA is a thousand volt-amperes, the unit of apparent power. Wikipedia defines apparent power as "the product of root mean square (RMS) current and voltage", and power factor as "the ratio of the real power absorbed by the load to the apparent power flowing in the circuit". Real power, in kW, is the part that does work. So kW = kVA x power factor.[1]

A generator is rated in both. The sheet of one maker's 80 kVA set states that all three-phase sets are rated at 0.8 power factor, and at 400 V gives 82.5 kVA and 66 kW for prime power (66 / 82.5 = 0.8). A generator maker's white paper puts it the same way: a 100 kVA three-phase set has a real power output of 80 kW (100 x 0.8). The 80 kVA sheet says single-phase sets are rated at 0.8 or 1.0 power factor, while the white paper treats single-phase sets as 1.0, so read the plate of a single-phase set.[2][3]

In South Africa supplies are also sized and partly billed in kVA. The national utility's 2026/27 tariff booklet sizes its Businessrate supplies, for urban customers with a notified maximum demand of up to 100 kVA, in kVA; the table below gives the three-phase sizes. It defines the notified maximum demand (NMD) as the contracted maximum demand, notified in writing by the customer and accepted by the utility, and its time-of-use tariff for urban customers with an NMD above 1 MVA bills several charges per kVA per month. How the power factor raises a bill is covered in power factor correction.[5]

A light tower carries a small alternator rated in kVA too: one brochure gives 5 kVA, and another sheet 7.5 kVA.[8][7]

How many amps is a given kVA on a three-phase supply?

Three-phase current follows from the white paper's kVA formula, kVA = 1.732 x V x I / 1000, solved for the current: I = kVA x 1000 / (1.732 x V), where 1.732 is the square root of three. At 400 V the divisor is 692.8, so 100 kVA is 144.3 A. The rows compare that arithmetic with the currents two sources state. The 82.5 kVA row agrees with the maker's sheet. The utility's booklet states each supply size with a current per phase but no voltage, and its currents are higher than the 400 V arithmetic; the booklet does not say why.[3][2][5]

How many amps is a given kVA on a three-phase supply?
RatingkVACurrent stated by the sourceArithmetic at 400 V (kVA x 1000 / 692.8)
National utility Businessrate, three-phase2540 A per phase36.1 A
National utility Businessrate, three-phase5080 A per phase72.2 A
National utility Businessrate, three-phase100150 A per phase144.3 A
One maker's 80 kVA set, prime power at 400 V82.5119.1 A rated current119.1 A

Sources:[5][2][3]

How do you add up the loads on a site, and what do motors do to the sum?

List every item the set must power, with its amps, voltage and phase, and for a motor its horsepower, nameplate code letter and how it starts: the mobile-generator paper says to work out the total kW, kVA or amps both to start and to run the load. A load given in kW becomes kVA when divided by its power factor, and a three-phase kW follows that paper's formula: 1.732 x V x I x PF / 1000.[3]

Motors are the difficulty. A second maker's paper on motor starting says starting current is typically six times a motor's rated full-load current, and stays high until the motor reaches about 75 percent of rated speed. It says a motor running at full load and rated speed normally needs less than one kVA per horsepower, and that sizing a set simply by matching its kVA to the motor's starting kVA would typically give more than twice the capacity necessary. It gives two reasons: motors start at a power factor of 0.3 to 0.5, against the 0.8 at which three-phase sets are usually rated, and the voltage dip during a start reduces the inrush current.[4]

Starting aids change the sum. The mobile-generator paper says soft starters and variable frequency drives are widely used to minimise the effect of motor starting kVA on generator sizing, and that single-phase induction motors need 3 to 5 times the amps or watts to start. Give the supplier each large motor's kW, phase and how it starts (direct on line, star-delta, soft starter or drive).[3]

Is a generator rated prime or standby, and who may connect it?

The two ratings are not the same kVA: at 400 V the same sheet gives 82.5 kVA and 66 kW for prime power and 91 kVA and 73 kW for standby. It defines prime power as available continuously at variable load in place of purchased power for an unlimited number of hours a year, and standby power as emergency power in the event of a utility power failure, both in accordance with ISO 8528-1. It gives no running-hours limit for standby, so ask the supplier for the maker's own.[2]

Connection is regulated. The Electrical Installation Regulations, 2009 do not name generators, but they count the connection of machinery at its supply terminals and the modification of an electrical installation as installation work (regulation 1). A registered person must exercise general control over all electrical installation work, and no person may allow such work without that control (regulation 5(4)); only a registered person may issue a certificate of compliance (regulation 9(1)). The generator hire page sets out the certificate duties, and SANS 10142-1 the wiring code behind them.[6]

A worked example

A site on a three-phase 400 V supply has running loads of 60 kW at 0.8 power factor. That is 60 / 0.8 = 75 kVA, and 75 x 1000 / 692.8 = 108.3 A. The 80 kVA sheet gives 82.5 kVA, 66 kW and 119.1 A at prime rating, so the set carries the running load, at 60 / 66 = 91% of its prime kW: above the 70 to 85% of rated capacity the mobile-generator paper calls the optimum. A motor start comes on top. The motor-starting paper's example, a 50 hp Code F motor at 5.59 locked-rotor kVA per hp, needs 50 x 5.59 = 279.5 kVA to start at full voltage, and the same paper says matching a set's kVA to that figure would typically give more than twice the capacity necessary. That is why the request must name the biggest motor and how it starts.[3][2][4]

Questions buyers ask

Is kVA the same as kW?

No. kVA is apparent power, the product of RMS current and voltage, and kW is the real power that does the work: kW = kVA x power factor. The lower the power factor, the wider the gap. The motor-starting paper gives motors a starting power factor of 0.3 to 0.5, so during a start a motor draws two to more than three times as many kVA as kW (1 / 0.5 = 2, 1 / 0.3 = 3.3).[1][4]

How many amps does a 100 kVA generator give?

On a three-phase 400 V supply, 100 x 1000 / (1.732 x 400) = 144.3 A, from the white paper's kVA formula (kVA = 1.732 x V x I / 1000) solved for the current. The 80 kVA sheet states 119.1 A for its 82.5 kVA prime rating at 400 V, which the same formula gives.[3][2]

What does NMD mean on a national utility account?

Notified maximum demand: the contracted maximum demand, notified in writing by the customer and accepted by the utility, for each point of supply. On its time-of-use tariff for supplies above 1 MVA, several R/kVA charges are based on the annual utilised capacity, which the booklet defines as the higher of the NMD or the maximum demand measured in kVA over a rolling 12 months.[5]

Do I need prime or standby for a site generator?

A set that runs in place of purchased power for weeks is a prime-power job: the maker's sheet defines prime as available continuously for an unlimited number of hours a year. Standby is defined for a utility power failure. State the use and hours in the request.[2]

Tell us about the power you need

Sources

  1. Wikipedia, Power factor, Last edited 12 August 2026.
  2. Tide Power (data sheet hosted by Multilec), 80 kVA diesel generator set, Lister Petter engine: technical data, file dated 28 March 2024 (PDF metadata).
  3. Generac Mobile, Basic Sizing for Mobile Generators (white paper by Dave Murphy), file created 29 May 2020 (PDF metadata).
  4. Kohler Power Systems, Sizing Generators for Motor Starting (Power Systems Topics 103), April 2024 (KPS 103 04/24, printed on the document).
  5. Eskom, Tariffs and Charges Booklet 2026/2027, Charges for non-local authorities from 1 April 2026 to 31 March 2027 (PDF created 2 July 2026).
  6. Department of Labour (Government Gazette 31975), Electrical Installation Regulations, 2009 (GN R. 242), 6 March 2009.
  7. Atlas Copco, HiLight V4 metal halide light tower, product page (Canada), undated (footer © 2026); read November 2026.
  8. Atlas Copco Power and Flow, HiLight light towers, full range brochure (United States), 2024.