What is a light tower, and how long does one run?

Light tower: a trailer carrying a telescopic mast and floodlights, powered by its own diesel generator, a battery, both, or an outside supply, towed to a work area that needs light after dark.[5][7][6]

Also called Lighting tower, Mobile lighting tower, Mobile light tower

  • A light tower stands on a trailer and raises four floodlights on a mast of about 7 to 9 metres. The makers' sheets read here cover metal halide or LED lamps on a diesel set, hybrids that add a battery, and one electric tower that connects to another power source.
  • Run time depends on the lamp output and the tank: the sheets read here give 50 hours for metal halide and 145 hours for LED on a diesel set (150 hours in that brochure's text), and for one hybrid at full output 125 hours on the generator and 180 hours in hybrid mode. Each is on its own basis, so ask for the figure at your output.
  • On a South African site the employer must meet the lux values in Table 6 of the Physical Agents Regulations, 2024, which replace the 1987 lighting rules: 20 to 200 lux for work areas and 50 lux for traffic areas.

Need one?TLB hire with an operatorPlant hire

Headcore8 sources

What work do you need done?

What is a light tower and where is it used?

A light tower is a mobile lighting set: a trailer with a telescopic mast, four floodlights at the top and a power source on the chassis. The makers' sheets read for this page list uses on road works, construction sites, events, mining operations, emergency response and lighting for crane work.[5][8]

The lamps are metal halide or LED. One maker's brochure says in its text that its LED lamps have a life expectancy of more than 30,000 hours, while its graphics show a 50,000-hour life span.[5]

The power is a small diesel engine and alternator, or a battery, or both. One sheet describes four operating modes: battery, diesel, hybrid and mains. On the hybrid sheet in the table below, hybrid mode runs 180 hours at full output against 125 hours from the generator alone.[8][6]

Its spare power is small next to its alternator: one brochure gives 1 kW of auxiliary power against a 5 kVA alternator, and another sheet lists outlet power with the lamps on as 1,000 / 2,000 W against a 7.5 kVA alternator. For power to run equipment, see generator hire.[5][4]

What types of light tower are there, and how long do they run?

The four rows come from four sheets by three makers, read in November 2026. They are examples, not a market survey, and each run time is the sheet's own figure on its own basis.[4][5][6][7]

What types of light tower are there, and how long do they run?
TypeMastLampsPowerRun time as the sheet states it
Metal halide, diesel set25 ft, manual, 5 sections4 × 1,000 W metal halide, 4 × 110,000 lumenDiesel engine 9.9 kW net in its table (its text says an 8 kW engine), alternator 7.5 kVA50 h on a 28 gallon tank; the page gives no load or conditions
LED, diesel set25 ft, manual, 5 sections4 × 350 W LEDDiesel engine 3 kW net, alternator 5 kVA145 h on a 28 gallon tank in its table; its text says a maximum of 150 h
LED, diesel and battery hybrid8,200 mm, hydraulic4 × 240 W LED, up to 139,200 lumen, adjustable from 25% to 100%Diesel engine, alternator 5 kVA, AGM battery; tank 100 L (90 L net)At 100% output: battery 3 h 45 min, generator 125 h, hybrid 180 h. At 25% output: 19 h 46 min, 165 h, 471 h
LED, diesel and lithium battery hybrid9.00 m, hydraulic, raised in 25 seconds4 × 200 W LED, 160,000 lumenDiesel engine, 52 V generator, 205 A h lithium battery; tank 100 L, 1.4 L/hrBattery 11 h before recharge (100% output to 70% depth of discharge, then 25% output to 80%); no diesel-only hours given

Sources:[4][5][6][7]

How much light must a South African site have?

Regulation 11(1) of the Physical Agents Regulations, 2024 (Notice 5952, Gazette 52226 of 6 March 2025) has the employer or self-employed person provide illumination in the workplace, natural, artificial or a combination. Regulation 11(4)(a)(ii) requires illuminance at an exterior workplace to be in accordance with the minimum maintained average values in Table 6, or Table 7 where the workplace is not listed.[1]

Table 6 has a Building Sites block. For a work area or task it sets a minimum maintained average of 20 lux for very rough work, 50 lux for rough work, 100 lux for accurate work and 200 lux for fine work. It sets 50 lux for traffic areas (pedestrian passages, vehicle turning, loading and unloading points) and 50 lux for safety and security, which covers general lighting on the building site, element mould, timber and steel storage, and the building foundation hole and the working areas on its sides.[1]

Regulation 11(4)(c)(iii) adds the minimum uniformity ratios in Table 6: for building sites, 0,25 for very rough work, 0,4 for rough and accurate work and for the two 50 lux rows, and 0,5 for fine work. Regulation 11(2) makes the employer take glare, flicker and the stroboscopic effect into account as far as reasonably practicable, and regulation 11(8)(f) has an illumination measurement and monitoring programme follow the principles and methodology in SANS 10389-1 for exterior lighting.[1]

These regulations replace the lighting rules of the Environmental Regulations for Workplaces, 1987 (GN R. 2281 of 16 October 1987). Regulation 21 says the 1987 regulations "will be repealed 18-months after the date of promulgation of the Physical Agents Regulations", so check that a guide you read quotes regulation 11 and Table 6, not the 1987 text. A notice of 20 February 2026 (Notice 7149) amended other parts of the regulations, and in Table 6 only the canals and locks rows.[1][2]

The Construction Regulations, 2014 (GN R. 84) set no lux value. Regulation 14(4)(f) has a contractor doing demolition work cause every stairwell used and every floor where work is being performed in a building being demolished to be adequately illuminated, by natural or artificial means, and regulation 23(2)(g) requires all mobile plant to have at least two headlights and two taillights in operation whenever visibility conditions warrant additional lighting. See construction regulations duties for the contractor's wider duties.[3]

What should you ask for when you hire a light tower?

Start from the lux you must reach, not from a lamp wattage. Check the light level behind any lit area a sheet quotes: one brochure claims up to 53,820 ft² of coverage (about 5,000 m², converted) at an average of 20 lux, and another sheet's isolux plot shows the area for each of 5, 10, 20, 50, 100 and 200 lux.[5][7]

In practice, put these in the request:[5]

  • The area to light, the task on it and the lux you must reach under Table 6, with an isolux plot or the maker's figure at that lux.[1][7]
  • The hours a night and the number of nights, with the run time at the lamp output you will use, since one sheet's battery hours run from 3 h 45 min at full output to 19 h 46 min at a quarter.[6]
  • The mast height and the wind rating in the maker's manual: the sheets read give 80 km/h (51 mph) on one page, 80 mph (about 129 km/h, converted) in one brochure, 100 km/h and 110 km/h.[4][5][7][6]
  • Who refuels the tank, and the noise at 7 m if people work or sleep close by: the sheets give 63 dB(A), below 65 dB(A) and up to 58 dB(A).[5][7][6]
  • The ground and the access: the sheets show outriggers or a four-point levelling system for the stand, and the weights they give run from 1,544 lb (about 700 kg, converted) to an aggregate trailer mass of 1,150 kg.[7][5]

A worked example

A contractor needs general lighting on a 40 m by 100 m timber and steel storage area on a building site, 4,000 m², for 12 hours a night. Table 6 sets 50 lux there, under safety and security. A brochure that claims about 5,000 m² (converted from 53,820 ft²) states it at an average of 20 lux, the value for very rough work, so it does not show 50 lux over 4,000 m²: ask for the plot at 50 lux. On run time, a sheet that gives 125 h from the generator at full output lasts 125 ÷ 12 = 10.4 nights of 12 hours before a refill, and 165 h at 25% output lasts 165 ÷ 12 = 13.75 nights.[1][5][6]

Questions buyers ask

How many lux must a building site have?

Table 6 of the Physical Agents Regulations, 2024 sets, for building sites, 20 lux for very rough work, 50 lux for rough work, 100 lux for accurate work and 200 lux for fine work. It sets 50 lux for traffic areas and 50 lux for safety and security, which covers general lighting on the site, timber and steel storage and the building foundation hole.[1]

Are the 1987 Environmental Regulations still the lighting rule?

They are being replaced. Regulation 21 of the Physical Agents Regulations, 2024, published on 6 March 2025, says the Environmental Regulations for Workplaces, 1987 will be repealed 18 months after the date of promulgation of the Physical Agents Regulations. Illumination is regulation 11 of the new regulations, with exterior values in Table 6.[1]

What is the difference between metal halide and LED light towers?

The sheets read here show four 1,000 W metal halide lamps with 50 hours on a 28 gallon tank, against four 350 W LED lamps with 145 hours on the same tank size (150 hours in that brochure's text). The metal halide set's table rates its engine at 9.9 kW net, though its text says 8 kW; the LED set's is 3 kW.[4][5]

What does a hybrid light tower do?

It adds a battery to the diesel set. One sheet gives 180 hours in hybrid mode at full output, against 125 hours from the generator alone and 3 h 45 min on battery alone, with lamp output adjustable from 25% to 100%.[6]

What work do you need done?

Sources

  1. Department of Employment and Labour (Government Gazette 52226), Physical Agents Regulations, 2024 (Notice 5952), 6 March 2025.
  2. Department of Employment and Labour (Government Gazette 54177), Amendment of the Physical Agents Regulations (Notice 7149), 20 February 2026.
  3. Department of Labour (Government Gazette 37305), Construction Regulations, 2014 (GN R. 84), 7 February 2014.
  4. Atlas Copco, HiLight V4 metal halide light tower, product page (Canada), undated (footer © 2026); read November 2026.
  5. Atlas Copco Power and Flow, HiLight light towers, full range brochure (United States), 2024.
  6. Generac Mobile (sheet hosted by a UK hire firm), Hybrid Lighting Tower V20 Pro, technical data, file posted September 2023.
  7. JLG Industries (Australia), sheet hosted by a dealer, Metro-Hybrid lighting tower, specification sheet (R0325), March 2025 by its document code; file posted February 2026.
  8. Chicago Pneumatic, CPLT M26 Hybrid, technical specifications (United States), undated; read November 2026.